Codeofchina.com is in charge of this English translation. In case of any doubt about the English translation, the Chinese original shall be considered authoritative.
GB/T 7251 Low-voltage Switchgear and Controlgear Assemblies consists of the following parts:
——Part 1: General Rules
——Part 3: Distribution Boards Intended to be Operated by Ordinary Persons (DBO);
——Part 4: Particular Requirements for Assemblies for Construction sites (ACS);
——Part 5: Assemblies for Power Distribution in public Networks;
——Part 6: Busbar Trunking Systems (Busways);
——Part 7: Assemblies for Specific Applications such as Marinas, Camping Sites, Market Squares, Electric Vehicles Charging Stations.
——Part 8: General Technology Requirement for Intelligent Assemblies;
——Part 10: Guidance to Specifying Assemblies;
——Part 12: Power Switchgear and Controlgear Assemblies
This part is Part 3 of GB/T 7251.
This part is developed in accordance with the rules given in GB/T 1.1-2009.
This part replaces GB/T 7251.3-2006 Low-voltage Switchgear and Controlgear Assemblies - Part 3: Particular Requirements for Low-voltage Switchgear and Controlgear Assemblies Intended to Be Installed in Places Where Unskilled Persons Have Access for Their Use - Distribution Boards; the following technical changes have been made with respect to GB/T 7251.3-2006 (the previous edition):
——The relevant structure and technical contents are adjusted according to GB/T 7251.1-2013.
This part is used in conjunction with GB/T 7251.1-2013.The general rules of GB/T 7251.1-2013 are applicable to only the scope where they are cited. If chapter and clause, figure as well as Appendix of general rules are to be used, it shall be made clear by reference to GB/T 7251.1-2013, e.g. 1.2.3 of GB/T 7251.1-2013, Table 4 of GB/T 7251.1-2013 or Appendix A of GB/T 7251.1-2013.
Clauses with number 101, 102, 103, etc. are the additional clauses of the corresponding ones in GB/T 7251.1-2013.
Tables and figures newly-added in this part are counted from 101.
Appendixes newly-added in this part are named by letters AA, BB, etc.
This part is, by means of translation, identical to IEC 61439-3: 2012 Low-voltage Switchgear and Controlgear Assemblies - Part 3: Part 3: Distribution Boards Intended to be Operated by Ordinary Persons (DBO).
The Chinese counterparts of the international documents given as normative references in this part are as follows:
——GB/T 2423.55-2006 Environmental Testing for Electric and Electronic Products - Part 2: Test Methods - Test Eh: Hammer Tests (IEC 60068-2-75: 1997, IDT);
——GB/T 10963.1-2005 Electrical Accessories - Circuit-breakers for Overcurrent Protection for Household and Similar Installation - Part 1: Circuit-breakers for a.c. Operation (IEC 60898-1: 2002, IDT);
——GB/T 22794-2008 Type B Residual Current Operated Circuit-breakers with and without Integral Overcurrent Protection for Household and Similar Uses (Type B RCCBs and Type B RCBOs) (IEC 62423: 2007, IDT).
The following editorial changes were made in this part:
——The contents of amendment to international standard are incorporated into this part.
This part was proposed by China Electrical Equipment Industry Association.
This part is under the jurisdiction of SAC/TC 266 National Technical Committee on Low-voltage Switchgear and Controlgear Assemblies of Standardization Administration of China.
The previous editions of the standard replaced by this Part are as follows:
——GB 7251.3-1997 and GB/T 7251.3-2006.
Low-voltage Switchgear and Controlgear Assemblies - Part 3: Distribution Boards Intended to Be Operated by Ordinary Persons (DBO)
鉚螺母低壓成套開關設備和控制設備
第3部分:由一般人員操作的配電板(DBO)
1 Scope
This part of GB/T 7251 defines the specific requirements for distribution boards intended to be operated by ordinary persons (DBO).
DBOs have the following criteria:
——intended to be operated by ordinary persons (e.g. switching operations and replacing fuse links), e.g. in domestic (household) applications;
——outgoing circuits contain protective devices, intended to be operated by ordinary persons, complying e.g. with IEC 60898-1, IEC 61008, IEC 61009, IEC 62423 and IEC 60269-3;
——rated voltage to earth does not exceed 300 V a.c.;
——rated current (Inc) of the outgoing circuits does not exceed 125 A and the rated current (InA) of the DBO does not exceed 250 A;
——intended for the distribution of electrical energy;
——enclosed, stationary;
——for indoor or outdoor use.
DBOs may also include control and/or signaling devices associated with the distribution of electrical energy.
This part applies to all DBOs whether they are designed, manufactured and verified on a one-off basis or fully standardized and manufactured in quantity.
DBOs may be assembled outside the factory of the original manufacturer.
This part does not apply to individual devices and self-contained components, such as circuit breakers, fuse switches, electronic equipment, etc. which will comply with the relevant product standards.
This standard does not apply to the specific types of ASSEMBLIES covered by other parts of GB/T 7251.
2 Normative References
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
Chapter 2 of GB/T 7251.1-2013 applies except as follows.
Addition:
GB/T 7251.1-2013 Low-voltage Switchgear and Controlgear Assemblies - Part 1: General Rules (IEC 61439-1: 2011, IDT)
IEC 60068-2-75 Environmental Testing - Part 2: Tests - Test Eh: Hammer Tests
IEC 60269-3 Low-voltage Fuses - Part 3: Supplementary Requirements for Fuses for Use by Unskilled Persons (Fuses Mainly for Household and Similar Applications) - Examples of Standardized Systems of Fuses A to F
IEC 60898-1: 2010 Electrical Accessories - Circuit-breakers for Overcurrent Protection for Household and Similar Installations - Part 1: Circuit-breakers for a.c. Operation
IEC 61008 (all parts) Residual Current Operated Circuit-breakers without Integral Overcurrent Protection for Household and Similar Uses(RCCBs)
IEC 61009 (all parts) Residual Current Operated Circuit-breakers with Integral Overcurrent Protection for Household and Similar Uses(RCBOs)
IEC 62423: 2009 Type F and Type B Residual Current Operated Circuit-breakers with and without Integral Overcurrent Protection for Household and Similar Uses
3 Terms and Definitions
Chapter 3 of GB/T 7251.1-2013 applies except as follows.
3.1 General terms
Additional terms:
3.1.101
Distribution board intended to be operated by ordinary persons (DBO)
Assembly used to distribute electrical energy in domestic (household) applications and other places where operation is intended by ordinary persons
Note: Switching operations and replacing fuse-links are examples of operations intended to be carried out by normal persons.
3.1.102
Type A DBO
DBO designed to accept single pole devices
Note: In the UK, a type A DBO used principally for domestic (household) installations and having a maximum incoming unit rating of 100 A and a maximum outgoing circuit rating of 63 A, is known as a "consumer unit" or "customer distribution board".
3.1.103
Type B DBO
DBO designed to accept multi-pole and/or single pole devices
4 Symbols and Abbreviations
Chapter 4 of GB/T 7251.1-2013 applies.
5 Interface Characteristics
Chapter 5 of GB/T 7251.1-2013 applies except as follows.
5.1 General
Addition:
This objective can be achieved through one of two typical processes; the user will either select a catalogue product, the characteristics of which meet the required user needs, or make a specific agreement with the manufacturer.
In both cases, the specification schedule according to Appendix AA is intended to help the user to provide all data necessary to specify, and to help the manufacturer to characterize the actual DBO. In some cases information declared by the DBO manufacturer may take the place of an agreement.
5.2.4 Rated impulse withstand voltage (Uimp) (of the assembly)
Replacement:
The rated impulse withstand voltage shall be equal to or higher than the values stated for the transient overvoltages occurring in the electrical system(s) to which the circuit is designed to be connected.
DBO’s shall comply with a minimum overvoltage category III (see IEC 60364-4-44) according to Table G.1 of Appendix G of GB/T 7251.1-2013.
5.4 Rated diversity factor (RDF)
Addition:
In the absence of an agreement between the DBO manufacturer and user concerning the actual load currents, the assumed loading of the outgoing circuits of the DBO or group of outgoing circuits may be based on the values in Table 101.
5.6 Other characteristics
Addition:
q) type A or type B DBO (see 3.1.102 and 3.1.103).
6 Information
Chapter 6 of GB/T 7251.1-2013 applies except as follows.
6.1 Assembly designation marking
Addition to first paragraph:
The test of 10.2.7 only applies to DBOs intended for outdoor installation.
Note: In Germany and Sweden, 10.2.7 applies to DBOs intended for indoor installation.
Addition of the following new items:
e) rated current of the DBO using the symbol InA, e.g. InA 250 A;
f) degree of protection if greater than IP 2XC.
7 Service Conditions
Chapter 7 of GB/T 7251.1-2013 applies except as follows.
7.1.3 Pollution degree
Addition:
A minimum pollution degree 2 applies.
Foreword i
1 Scope
2 Normative References
3 Terms and Definitions
4 Symbols and Abbreviations
5 Interface Characteristics
6 Information
7 Service Conditions
8 Constructional Requirements
9 Performance Requirements
10 Design Verification
11 Routine Verification
Annexes
Annex D (Informative) Design Verification
Annex AA (Informative) Items Subject to Agreement between the Assembly Manufacturer and the User
Bibliography
Figure 101 Example of the Temperature Rise Verification by Test of a Complete DBO as in 10.10.2.
Table 101 Values of Assumed Loading
Table 102 Tightening Torque Vaelues for the Verification of Mechanical Strength
Table AA.1 Items Subject to Agreement between the Assembly Manufacturer and the User
ICS 29.130.20
K 31
中華人民共和國國家標準
GB/T 7251.3—2017/IEC 61439-3:2012
代替GB/T 7251.3—2006
低壓成套開關設備和控制設備
第3部分:由一般人員操作的配電板(DBO)
Low-voltage switchgear and controlgear assemblies—Part 3:Distribution boards
intended to be operated by ordinary persons(DBO)
(IEC 61439-3:2012,IDT)
2017-11-01發(fā)布 2018-05-01實施
中華人民共和國國家質量監(jiān)督檢驗檢疫總局
中國國家標準化管理委員會
發(fā)布
前言
GB/T 7251《低壓成套開關設備和控制設備》分為以下部分:
——第1部分:總則;
——第3部分:由一般人員操作的配電板(DBO);
——第4部分:對建筑工地用成套設備(ACS)的特殊要求;
——第5部分:公用電網電力配電成套設備;
——第6部分:母線干線系統(tǒng)(母線槽);
——第7部分:特定應用的成套設備——如碼頭、露營地、市集廣場、電動車輛充電站;
——第8部分:智能型成套設備通用技術要求;
——第10部分:規(guī)定成套設備的指南;
——第12部分:成套電力開關和控制設備。
本部分為GB/T 7251的第3部分。
本部分按照GB/T 1.1—2009給出的規(guī)則起草。
本部分代替GB/T 7251.3—2006《低壓成套開關設備和控制設備 第3部分:對非專業(yè)人員可進入場地的低壓成套開關設備和控制設備——配電板的特殊要求》,與GB/T 7251.3—2006相比主要技術變化如下:
——有關結構和技術部分的內容按GB/T 7251.1—2013調整。
本部分與GB/T 7251.1—2013結合使用。GB/T 7251.1—2013的總則條款只適用于本部分明確引用的范圍。如果應用總則的章和條、表格、圖和附錄,則通過參考GB/T 7251.1—2013指明,例如,GB/T 7251.1—2013的1.2.3、GB/T 7251.1—2013的表4,或GB/T 7251.1—2013的附錄A。
帶有號碼101、102、103等的條是GB/T 7251.1—2013中相同條的附加條款。
本部分中新增的表格和圖從101開始計數。
本部分中新增的附錄以字母AA,BB等命名。
本部分使用翻譯法等同采用IEC 61439-3:2012《低壓成套開關設備和控制設備 第3部分:由一般人員操作的配電板(DBO)》。
與本部分中規(guī)范性引用的國際文件有一致性對應關系的我國文件如下:
——GB/T 2423.55—2006 電工電子產品環(huán)境試驗 第2部分:試驗方法 試驗Eh:錘擊試驗(IEC 60068-2-75:1997,IDT);
——GB/T 10963.1—2005 電氣附件 家用及類似場所用過電流保護斷路器 第1部分:用于交流的斷路器(IEC 60898-1:2002,IDT);
——GB/T 22794—2008家用和類似用途的不帶和帶過電流保護的B型剩余電流動作斷路器(B型RCCB和B型RCBO)(IEC 62423:2007,IDT)。
本部分做了下列編輯性修改:
——本部分納入國際標準修改單的內容。
本部分由中國電器工業(yè)協(xié)會提出。
本部分由全國低壓成套開關設備和控制設備標準化技術委員會(SAC/TC 266)歸口。
本部分起草單位:天津電氣科學研究院有限公司、天津天傳電控配電有限公司、國家電控配電設備質量監(jiān)督檢驗中心(天津天傳電控設備檢測有限公司)、鎮(zhèn)江市產品質量監(jiān)督檢驗中心、福建森達電氣股份有限公司、遠東電器集團有限公司、浙江方圓電氣設備檢測有限公司、杭州九川電氣有限公司、山東魯億通智能電氣股份有限公司、成都市產品質量監(jiān)督檢驗院、波瑞電氣有限公司、湖南電器科學研究院、浙寶電氣(杭州)集團有限公司、寧波奇奧電氣科技集團有限公司、深圳市光輝電器實業(yè)有限公司、寧夏力成電氣集團有限公司。
本部分主要起草人:劉潔、王陽、盧林、崔維峰、陳澤銀、李仕榮、黃芳、劉曉林、徐克峰、馮彪、朱文堂、陳可夫、林必寶、馮群俠、蔡宗光、牛廣軍。
本部分所代替標準的歷次版本發(fā)布情況為:
——GB 7251.3—1997、GB/T 7251.3—2006。
低壓成套開關設備和控制設備
第3部分:由一般人員操作的
配電板(DBO)
1 范圍
GB/T 7251的本部分定義了由一般人員操作的配電板(DBO)的具體要求。
DBO具有以下條件:
——擬由一般人員進行操作(例如開關操作和更換熔斷體),例如在民用(家用)的應用中;
——出線電路包含擬由一般人員操作、符合下列標準的保護器件,如IEC 60898-1、IEC 61008、IEC 61009、IEC 62423和IEC 60269-3;
——對地額定電壓不超過交流300 V;
——出線電路的額定電流(Inc)不超過125 A且DBO的額定電流(InA)不超過250 A;
——擬用于電能分配;
——封閉式,固定式安裝;
——用于戶內或戶外。
DBO可包括與電能分配相關的控制和/或信號器件。
本部分適用于所有DBO,無論其是一次性設計、制造和驗證的,還是完全標準化批量制造的。
DBO可在初始制造商工廠以外組裝。
本部分不適用于符合各自相關產品標準的單獨器件和整裝元件,例如斷路器、刀熔開關、電子設備等。
本部分不適用于包含在GB/T 7251其他部分的特定類型成套設備。
2規(guī)范性引用文件
下列文件對于本文件的應用是必不可少的。凡是注日期的引用文件,僅注日期的版本適用于本文件。凡是不注日期的引用文件,其最新版本(包括所有的修改單)適用于本文件。
除以下內容外,GB/T 7251.1—2013的第2章適用。
增加:
GB/T 7251.1—2013低壓成套開關設備和控制設備 第1部分:總則(IEC 61439-1:2011,IDT)
IEC 60068-2-75環(huán)境試驗 第2部分:試驗 試驗Eh:錘擊試驗(Environmental testing—Part 2:Tests—Test Eh:Hammer tests)
IEC 60269-3低壓熔斷器 第3部分:非熟練人員使用的熔斷器的補充要求(主要用于家用和類似用途的熔斷器)—標準化熔斷器體系示例A至F[Low-voltage fuses—Part 3:Supplementary require-ments for fuses for use by unskilled persons(fuses mainly for household and similar applications)—Examples of standardized systems of fuses A to F]
IEC 60898-1:2010 電氣附件 家用及類似場所用過電流保護斷路器 第1部分:用于交流的斷路器[Electrical accessories—Circuit-breakers for overcurrent protection for household and similar in-stallations—Part 1:Circuit-breakers for a.c.operation]
IEC 61008(所有部分)家用和類似用途的不帶過電流保護的剩余電流動作斷路器(RCCB)[Re-sidual current operated circuit-breakers without integral overcurrent protection for household and sim-ilar uses(RCCBs)(all parts)]
IEC 61009(所有部分)家用和類似用途的帶過電流保護的剩余電流動作斷路器(RCBO)[Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses(RCBOs)(all parts)]
IEC 62423:2009家用和類似用途的不帶和帶過電流保護的F型和B型剩余電流動作斷路器[Type F and type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses]
3術語和定義
除以下內容外,GB/T 7251.1—2013的第3章適用。
3.1 通用術語
增加術語:
3.1.101
由一般人員操作的配電板(DBO)distribution board intended to be operated by ordinary persons(DBO)
擬由一般人員操作,為民用(家用)應用和其他場所分配電能的成套設備。
注:開關操作和更換熔斷體是由一般人員進行操作的例子。
3.1.102
A型DBO type A DBO
設計為可安裝單極器件的DBO。
注:在英國,主要用于民用(家用)設備,并且最大進線單元額定值為100A和最大出線單元額定值為63A的A型DBO被認為是“用戶單元”或“用戶配電板”。
3.1.103
B型DBO type B DBO
設計為可安裝多極和/或單極器件的DBO。
4符號和縮略語
GB/T 7251.1—2013的第4章適用。
5接口特性
除以下內容外,GB/T 7251.1—2013的第5章適用。
5.1 通則
增加:
此目標可通過兩個典型步驟之一來實現(xiàn):用戶可選擇一個特性滿足用戶要求的目錄中的產品,或與制造商達成具體協(xié)議。
在這兩種情況下,依據附錄AA的詳細清單,可幫助用戶提供他所需要規(guī)定的所有數據,并幫助制造商描繪實際的DBO。在某些情況下,由DBO制造商給出的信息可取代協(xié)議。
5.2.4額定沖擊耐受電壓(Uimp)(成套設備的)
取代:
額定沖擊耐受電壓應等于或高于該電路預定連接的電氣系統(tǒng)中出現(xiàn)的瞬時過電壓的規(guī)定值。
按照GB/T 7251.1—2013附錄G的表G.1,DBO應至少符合過電壓類別Ⅲ(見IEC 60364-4-44)。
5.4額定分散系數(RDF)
增加:
在DBO制造商和用戶間沒有關于實際負載電流的協(xié)議時,DBO的出線電路或出線電路組的計算負荷可基于表101的值。
5.6其他特性
增加:
q)A型或B型DBO(見3.1.102和3.1.103)。
6信息
除以下內容外,GB/T 7251.1—2013的第6章適用。
6.1 成套設備規(guī)定的標志
增加至第一段:
10.2.7的試驗僅適用于擬安裝于戶外的DBO。
注:在德國和瑞典,10.2.7也適用于擬安裝于戶內的DBO。
增加以下新項目:
e)DBO的額定電流使用符號InA,例如InA 250 A;
f)防護等級,如果高于IP 2XC。
7使用條件
除以下內容外,GB/T 7251.1—2013的第7章適用。
7.1.3污染等級
增加:
最低污染等級2適用。
8 結構要求
除以下內容外,GB/T 7251.1—2013的第8章適用。
8.2.1對機械碰撞的防護
取代:
按照IEC 62262,DBO應符合下列IK代碼:
——戶內使用的DBO為IK 05。
——戶外使用的DBO為IK 07。
應依據10.2.6驗證是否符合。
注:在美國,不需要IK代碼,因為“類型”標記適用的要求(見GB/T 7251.1—2013中8.2.2的注1)包含了對IK代碼的考慮。
8.2.2 防止觸及帶電部件以及固體異物和水的進入
取代第二段:
在按照DBO制造商的說明書安裝后,戶內安裝的DBO的防護等級應至少為IP 2XC。
8.4.6.2.5屏障
GB/T 7251.1—2013的此條不適用。
8.5.3 開關器件和組件的選擇
增加:
出線電路應包含擬由一般人員操作、符合下列標準的保護器件,如IEC 60898-1、IEC 61008、IEC 61009、IEC 62423和IEC 60269-3。
當DBO裝入不符合以上標準的器件時,進線保護器件的重新閉合,應需要鑰匙或工具。也可采用標簽說明此器件重新合閘只能由受過培訓的人員或熟練技術人員完成,此標簽應置于進線保護器件的附近。
斷路器的設計或安裝應在非故意行為時不能改變其整定值或刻度值,包括使用鑰匙或工具,并導致其整定值或刻度值的明顯改變。
當裝入DBO中的進線保護器件含有不符合IEC 60269—3熔斷體的熔斷器時,則在更換熔斷體時需要鑰匙或工具。
注:在挪威,用于建筑物中配線保護的出線單元中的保護器件應符合IEC 60898-1、IEC 61008、IEC 61009、IEC 60269-3或IEC 60947-2,除IEC 60898-1:2001的9.10.1或IEC 61009-1:2010的9.9.2.1規(guī)定的B型、C型和D型時間電流特性試驗以外,要滿足IEC 60898-1或IEC 61009所有其他試驗的要求。
8.6.1 主電路
取代第二段:
在進線單元與出線單元間以及這些單元內包含的組件間的每個導體,只要這些導體的布置使得在正常運行條件下,不會在相間和/或相與地之間發(fā)生內部短路(見GB/T 7251.1—2013的8.6.4),可按發(fā)生在各個出線短路保護器件負載端衰減后的短路應力為基礎來選擇其額定數據。
增加:
注:英國電力、安全和質量法規(guī)S.I.2002 No.2965要求供電部門說明電源端的最大預期短路電流。在英國,由供電局依據電力協(xié)會出版物第25頁規(guī)定的家用和類似電氣設備的電源端的最大預期短路電流對最大至100 A的單相電源為16 kA。
8.8外接導線端子
增加:
DBO中性端子數量應不少于為每個需要中性端子的出線電路配備一個端子。這些端子的放置或標識應與其相導體端子具有相同順序。
DBO應至少具有兩個用于電氣設備保護聯(lián)結導體的端子。
注:在美國,中性導體用白色標識,接地保護導體可由綠/黃或純綠來標識。
9 性能要求
GB/T 7251.1—2013的第9章適用。
10設計驗證
除以下內容外,GB/T 7251.1—2013的第10章適用。
10.2.2.2嚴酷試驗A
增加:
以下是一個可替代試驗:
將待試驗的DBO的鋼制外殼的部件或代表性樣品,在諸如三氯乙烷或精制汽油之類的冷的化學脫脂劑中浸泡10 min,以除去所有的潤滑油。再將部件放在溫度為(20±5)℃的10%氯化銨水溶液中浸泡10 min。
不需烘干,甩掉所有水滴后,將部件放置在溫度為(20±5)℃充滿飽和水蒸氣的容器里10 min。
將部件置于溫度為(100±5)℃的加熱箱中烘干10 min,并置于室溫下24 h后,其表面應無銹跡。
銳利邊緣上的銹痕和可擦去的所有黃印可忽略不計。
對于小螺旋彈簧和類似物,以及不可接近的易磨損部件,一層潤滑油可提供足夠防銹保護。此類部件僅在對潤滑油膜的有效性產生懷疑時進行試驗,且進行試驗不應去除原有潤滑油。
10.2.2.4試驗結果
GB/T 7251.1—2013的第一段不適用于本部分的可替代試驗。
10.2.3.2絕緣材料耐受內部電效應引起的非正常發(fā)熱和著火的驗證
GB/T 7251.1—2013的最后一段不適用。
增加:
注:850℃不適用于安裝于凹墻中的外殼的可接近部件,如覆板、門。
10.2.6機械碰撞
取代:
機械碰撞防護等級的驗證應依據IEC 62262進行。
試驗應通過IEC 60068-2-75中描述的錘擊試驗儀器進行,例如沖擊彈簧錘。戶內使用時樣品置于-5℃±1 K溫度下、戶外使用時樣品置于-25℃±1 K溫度下,放置2 h后,再進行試驗。
按正常使用安裝時,對可能遭受機械碰撞的DBO的裸露部件,應核查是否符合此要求。
帶有覆板或外殼的樣品,如果有,應如同正常使用一樣固定或倚靠剛性支撐架放置。
三次撞擊應施加在每個可接近的面和f-j(如果有)的不同部位。撞擊應均勻分布在受試外殼的面上。任何情況下不應在外殼同一點的周圍施加撞擊。除非先前的試驗沒有影響后續(xù)試驗結果,則樣品可重復使用外,每個可接近的面應使用新樣品。不應對敲落孔、符合其他標準的內裝組件,或為使其不受碰撞而置于表面下方凹陷處的其他緊固設施實施撞擊。
沒有配備敲落孔的電纜入口應打開。如果配備有敲落孔,則應打開其中的兩個。
在實施撞擊前,基座、覆板和類似裝置的固定螺釘應用與表102規(guī)定相等的扭力矩緊固。
試驗后,應目測驗證保持規(guī)定的IP代碼和介電性能。可移式覆板仍然能移出和恢復原位,門能打開和關閉。
10.2.7標志
新增第一段:
本試驗僅適用于擬安裝于戶外的DBO。
10.10.2.3.1 通則
在第3段后增加:
如果沒有制造商的說明書,則施加于端子上的擰緊力矩應符合相關器件產品標準中溫升試驗的規(guī)定。
10.10.2.3.6分別驗證各功能單元和整個成套設備
增加至第4段:
確定最嚴酷的組的一種方法為,DBO的額定電流(InA),在最少數量的出線電路中分配電流,使得每條電路承載其額定電流乘以本部分表101所示的計算負荷系數,或由制造商規(guī)定的分散系數。完整DBO的例子,見圖101。
10.10.2.3.7分別驗證各功能單元,主母線,配電母線和整個成套設備
增加至d)項:
確定最嚴酷的組的一種方法為,DBO的額定電流(InA),在最少數量的出線電路中分配電流,使得每條電路承載其額定電流乘以本部分表101所示的計算負荷系數,或由制造商規(guī)定的分散系數。
10.10.3.2成套設備
增加:
按照GB/T 7251.1—2013的表6,如果合成材料的外殼內表面的最高空氣溫升不超過可接近外部金屬表面的最大表面溫升,則認為合成材料外殼的DBO是有代表性的金屬外殼的DBO。
10.10.4.2.3結果
增加:
注:以最接近器件的指定周圍空氣溫度下的最大額定電流的形式提供指導。
例如:
a)本地周圍空氣溫度為40℃時,Ith=200 A,由此得出0.8×200 A=160 A。
b)外殼內的計算空氣溫度為60℃。制造商的信息表明在本地周圍空氣溫度為60℃時,器件的Ith極限為150 A。
結論:a)和b)中較小的值為連續(xù)允許負荷,在此情況下,計算出的本地空氣溫度下為150 A。
10.10.4.3.2結果
增加:
注:以最接近器件的指定周圍空氣溫度下的最大額定電流的形式提供指導。
例如:
a)本地周圍空氣溫度為40℃時,Ith=200 A,由此得出0.8×200 A=160 A。
b)外殼內的計算空氣溫度為60℃。制造商的信息表明在本地周圍空氣溫度為60℃時,器件的Ith極限為150 A。
結論:a)和b)中較小的值為持續(xù)允許負荷,在此情況下,計算出的本地空氣溫度下為150 A。
10.11.5.3.3進線電路和主母線
增加:
當連接到主母線的進線器件的負載端子與出線功能單元電源端子之間,主母線和配電母線間的距離不超過3 m時,可確定額定限制短路電流。只要在這些導體的布置不會發(fā)生相間和/或相與地間的內部短路(見GB/T 7251.1—2013的8.6.4)的條件下,主母線、配電母線和進線器件可基于每個單元內各自短路保護器件的負載端產生的衰減后的短路應力進行試驗和確定額定值。
注:導體類型和安裝要求的例子在GB/T 7251.1—2013的表4中給出。
10.13機械操作
取代第2段:
對于需要通過試驗驗證的部件,符合要求的機械操作應在安裝至DBO后進行驗證。操作循環(huán)次數應為50次。
11例行檢驗
除以下內容外,GB/T 7251.1—2013的第11章適用。
11.9介電性能
在第一段后增加:
介電試驗不要求在僅包含母線和/或預制主電路線路的DBO上進行,也不要求在目測足以確定導體和電纜包括適當敷設的簡單結構的DBO上進行。
增加表和圖:
表101計算負荷值
出線電路數量 計算負荷系數
2和3 0.8
4和5 0.7
6到9(包含9) 0.6
10及以上 0.5
表102用于驗證機械強度的扭緊力矩
螺紋直徑
mm 扭緊力矩
Nma
公制標準值
mm 直徑范圍
d
mm Ib Ⅱc Ⅲd
2.5
3.0
—
3.5
4
4.5
5
6
8
10 d≤2.8
2.8