Codeofchina.com is in charge of this English translation. In case of any doubt about the English translation, the Chinese original shall be considered authoritative.
This standard is developed in accordance with the rules given in GB/T 1.1-2009.
This standard replaces GB/T 13955-2005 Installation and Operation of Residual Current Operated Protective Devices; in addition to a number of editorial changes,the following technical changes have been made with respect to GB/T 13955-2005:
——GB/T 14048.1, GB/T 20044, GB/T 22387, GB/T 22794 and GB/T 28527 (see Chapter 2) are added;
——GB 14287 is deleted (see Chapter 2 of 2005 edition);
——The definitions of terms such as "direct contact", "indirect contact", "residual current" and "assemble type residual operated protective devices" are modified (see 3.1, 3.2, 3.3 and 3.29; 3.1, 3.2, 3.3 and 3.24 of 2005 edition);
——The terms and definitions of "group of loads", "selective protection", "main protection", "middle protection" and "end protection" are added (see 3.12, 3.13, 3.14, 3.15 and 3.16);
——Term and definition of "residual current operated electrical fire monitor system" is deleted (see 3.26 of 2005 edition);
——Restrictions to "power supply and consumption system for neutral point direct earthing of power supply" and to rated frequency are cancelled (see Chapter 1; Chapter 1 of 2005 edition);
——The relevant contents of "alarm RCD" and "residual current operated electrical fire monitor system" are deleted (see introduction);
——"5.4 c) The influence of non-power frequency leakage current shall be considered in occasions where the application of power line carrier has an influence on line leakage current." is added (see 5.4);
——The requirements of RCD installation in agricultural power utilization place in the rural area are added (see 4.4.1; 4.5.1 of 2005 edition);
——"Energy meter boxes are intensively installed in the rural area" is deleted (see 4.4.2; 4.5.2 of 2005 edition);
——TN-C earthing type in Table 1 is deleted (see Table 1; Table 1 of 2015 edition);
——Specific operation and management plans are proposed according to the relevant requirements for maintenance, operation and fault shooting of RCD; the relevant compulsory technical requirements in original standard are revised;
——Button test and on-load opening/closing after installation is changed as one time (see 6.3; 6.3.7 of 2005 edition).
This standard was proposed by and is under the jurisdiction of China Electricity Council.
The previous edition of the standard replaced by this standard is:
——GB/T 13955-2005.
Introduction
To install residual current operated protective devices in low-voltage distribution system is one of the effective measures for avoiding electric shock accident caused by direct and indirect contact, and it is also one of the technical measures for avoiding electrical fire and electrical equipment damage accident caused by earth fault of electrical circuit or electrical equipment. After residual current operated protective device is installed, the prevention shall come first, in addition, other technical measures for avoiding electric shock accident, electrical fire and electrical equipment damage accident shall also be taken.
The residual current operated protective device in this standard refers to the protective device being able to automatically power off when the residual current generated by earth fault of live conductor in circuit is greater than the specified value, including various circuit-breakers with residual current protection function, portable move type residual current operated protective devices and residual current relays and the composite apparatus.
Installation and Operation of Residual Current Operated Protective Devices
1 Scope
This standard specifies the relevant requirements for correct selection, installation and use of Residual Current operated protective Devices (hereinafter referred to as RCD) as well as its operation and management.
This standard is applicable to AC power supply and consumption system with rated voltage not greater than 400V.
This standard is not applicable to protection against electric shock accident happened between phases or between phase and N line, electrical equipment damage or electrical fire accident.
2 Normative References
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the normative document (including any amendments) applies.
GB/Z 6829 General Requirements for Residual Current Operated Protective Devices
GB/T 10963.1 Electrical Accessories - Circuit-breakers for Overcurrent Protection for Household and Similar Installation - Part 1: Circuit-breakers for a.c. Operation (GB/T 10963.1-2005, IEC 60898.1:2002, IDT)
GB/T 14048.1 Low-voltage Switchgear and Controlgear - Part 1:General Rules (GB/T 14048.1-2012, IEC 60947-1:2011, MOD)
GB/T 14048.2 Low-voltage Switchgear and Controlgear - Part 2: Circuit-breakers (GB/T 14048.2-2008, IEC 60947-2:2006, IDT)
GB 14050-2008 Types and Safety Technical Requirements of System Earthing
GB/T 16916 (All parts) Residual Current Operated Circuit-breakers without Integral Overcurrent Protection for Household and Similar Uses (RCCB) (GB/T 16916.1-2014, IEC 61008-11:2012, MOD; GB/T 16916.21-2008, IEC 61008-2-1:1990, IDT; GB/T 16916.22-2008, IEC 61008-2-2:1990, IDT)
GB/T 16917 (All parts) Residual Current Operated Circuit-breakers with Integral Overcurrent Protection for Household and Similar Uses (RCCB) (GB/T 16917.1-2014, IEC 61009-1:2012, MOD; GB/T 16917.21-2008, IEC 61009-2-1:1991, IDT; GB/T 16917.22-2008, IEC 61009-2-2:1991, IDT)
GB/T 20044 Electrical Accessories - Portable Residual Current Devices without Integral Overcurrent Protection for Household and Similar Use (PRCD) (GB/T 20044-2012, IEC 61540:1999, MOD)
GB/T 22387 Residual Current Operated Relay
GB/T 22794 Type B Residual Current Operated Circuit-breakers with and without Integral Overcurrent Protection for Household and Similar Uses (Type B RCCBs and Type B RCBOs) (GB/T 22794-2008, IEC 62423:2007, IDT)
GB/T 28527 Residual Current Devices with or without Overcurrent Protection for Socket-outlets for Household and Similar Uses (SRCD) (GB/T 28527-2012, IEC 62640:2011, MOD)
3 Terms and Definitions
For the purposes of this document, the following terms and definitions apply.
3.1
direct contact
contact of human or animal with live conductor
3.2
indirect contact
contact of human or animal with exposed conductor of equipment which becomes live under fault condition
3.3
residual current
I?
effective value of current vector sum passing through RCD main circuit
3.4
residual operating current
residual current value which causes RCD to operate under specified conditions
3.5
rated residual operating current
IΔn
residual operating current value of RCD specified by the manufacturer, at which RCD shall operate under specified conditions
3.6
residual non-operating current
residual current value which doesn't cause RCD to operate under specified conditions in case of less than or equal to this current
3.7
rated residual non-operating current
IΔn0
residual non-operating current value of RCD specified by the manufacturer, at which RCD will not operate under specified conditions
3.8
earth fault current
current flowing into the earth due to insulation fault
3.9
earth leakage current
current flowing into the earth from live component of equipment without insulation fault
3.10
residual current operated circuit-breaker
mechanical switching device used for connecting, carrying and disconnecting the current under normal operating conditions and disconnecting the contact when the residual current reaches the specified value under specified conditions
3.11
residual current operated relay
electric apparatus which can send out operating command when the residual current reaches the specified value under specified conditions
3.12
group of loads
set of all power loads sharing the same branch point
3.13
selective protection
RCD is respectively installed at power supply end, head end of group of loads and load end to constitute two-level or above series connection protective system, and the rated current value and residual current operated value of main circuit of RCD at all levels cooperate with the operating time to realize selective protection
3.14
main protection
Level 1 RCD installed at low-voltage side of distribution area, also known as Level 1 protection
3.15
middle protection
RCD installed at low-voltage main line or branch line between main protection and household protection, also known as Level 2 protection; middle protection may be classified into "three-phase middle protection" and "single-phase middle protection" according to different installation places and wiring modes
3.16
end protection
it refers to the power distribution protection of residential buildings (or household protection) or protection of single electric equipment (Level 3 protection)
3.17
residual current operated circuit-breaker without integral overcurrent protection
residual current operated circuit-breakers without overload and/or short-circuit protection functions
3.18
residual current operated circuit-breaker with integral overcurrent protection
residual current operated circuit-breakers with overload and/or short-circuit protection functions
3.19
RCD's functionally independent of line voltage
RCD, of which, the detection, judgment and disconnection functions are independent of line voltage
3.20
RCD's functionally dependent on line voltage
RCD, of which, the detection, judgment and disconnection functions are dependent on line voltage
3.21
break time of RCD
the period from the moment of suddenly applying residual operating current to the moment of all electrode arcs going off
3.22
limit non-actuating time
the maximum delay time of applying a residual current value greater than residual non-operating current on RCD but not causing RCD to operate
3.23
time-delay RCD
RCD specially designed for corresponding to a given residual current value and reaching a predetermined limit non-actuating time
3.24
type AC residual current device
RCD which can ensure to release the suddenly applied or slowly rising residual sinusoidal alternating current
Foreword i
Introduction iii
1 Scope
2 Normative References
3 Terms and Definitions
4 Application of RCD
4.1 Protection against Direct Contact Electric Shock Accident
4.2 Protection against Indirect Contact Electric Shock Accident
4.3 Selective Protection
4.4 Equipment and Place in Which RCD Shall be Installed
4.5 Situation Where RCD May not be Installed
5 Selection of RCD
5.1 Technical Conditions of RCD
5.2 Technical Parameters of RCD
5.3 Selection of RCD According to Power Supply Mode of Electrical Equipment
5.4 Selection of Rated Operating Current of RCD
5.5 Adoption of Selective Protection Mode
5.6 Selection of RCD According to Operating Environment Conditions of Electrical Equipment
5.7 Selection of Operating Parameters of RCD
5.8 Selection of RCD with Special Load and in Special Places
6 Installation of RCD
6.1 Installation Requirements of RCD
6.2 Requirements of RCD for Power Grid
6.3 Construction Requirements of RCD Installation
7 Operation and Management of RCD
Annex A (Normative) System Earthing Types
Annex B (Normative) Rated Value of RCD
Annex C (Informative) Reference of Selective Protection Mode
Bibliography
剩余電流動作保護裝置安裝和運行
1 范圍
本標準規定了正確選擇、安裝、使用剩余電流動作保護裝置(Residual Current operated protective Devices,簡稱RCD)及其運行管理的有關要求。
本標準適用于額定電壓不超過400 V的交流供用電系統。
本標準不適用于相與相之間或相與N線之間發生的電擊事故、電氣設備損壞或電氣火災事故的保護作用。
2規范性引用文件
下列文件對于本文件的應用是必不可少的。凡是注日期的引用文件,僅注日期的版本適用于本文件。凡是不注日期的引用文件,其最新版本(包括所有的修改單)適用于本文件。
GB/Z 6829剩余電流動作保護器的一般要求
GB/T 10963.1電氣附件 家用及類似場所用過電流保護斷路器 第1部分:用于交流的斷路器(GB/T 10963.1—2005,IEC 60898.1:2002,IDT)
GB/T 14048.1低壓開關設備和控制設備 第1部分:總則(GB/T 14048.1—2012,IEC 60947—1:2011,MOD)
GB/T 14048.2低壓開關設備和控制設備 第2部分:斷路器(GB/T 14048.2—2008,IEC 60947—2:2006,IDT)
GB 14050—2008系統接地的型式及安全技術要求
GB/T 16916(所有部分) 家用和類似用途的不帶過電流保護的剩余電流動作斷路器(RCCB)(GB/T 16916.1—2014,IEC 61008-11:2012,MOD;GB/T 16916.21—2008,IEC 61008-2-1:1990,IDT;GB/T 16916.22—2008,IEC 61008—2—2:1990,IDT)
GB/T 16917(所有部分) 家用和類似用途的帶過電流保護的剩余電流動作斷路器(RCBO)(GB/T 16917.1—2014,IEC 61009—1:2012,MOD;GB/T 16917.21—2008,IEC 61009—2—1:1991,IDT;GB/T 16917.22—2008,IEC 61009—2—2:1991,IDT)
GB/T 20044電氣附件 家用和類似用途的不帶過電流保護的移動式剩余電流裝置(PRCD)(GB/T 20044—2012,IEC 61540:1999,MOD)
GB/T 22387剩余電流動作繼電器
GB/T 22794家用和類似用途的不帶或帶過電流保護的B型剩余電流動作斷路器(B型RCCB和B型RCBO)(GB/T 22794—2008,IEC 62423:2007,IDT)
GB/T 28527 家用和類似用途的帶或不帶過電流保護的插座式剩余電流電器(SRCD)(GB/T 28527—2012,IEC 62640:2011,MOD)
3術語和定義
下列術語和定義適用于本文件。
3.1
直接接觸direct contact
人、動物與帶電導體的接觸。
3.2
間接接觸indirect contact
人、動物與故障情況下變為帶電的設備外露導體的接觸。
3.3
剩余電流residual current
IA
通過RCD主回路的電流矢量和的有效值。
3.4
剩余動作電流residual operating current
使RCD在規定條件下動作的剩余電流值。
3.5
額定剩余動作電流rated residual operating current
IΔn
制造廠對RCD規定的剩余動作電流值。在該電流值時,RCD應在規定的條件下動作。
3.6
剩余不動作電流residual non-operating current
在小于或等于該電流時,RCD在規定條件下不動作的剩余電流值。
3.7
額定剩余不動作電流 rated residual non-operating current
IΔn0
制造廠對RCD規定的剩余不動作電流值,在該電流值時,RCD在規定的條件下不動作。
3.8
接地故障電流earth fault current
由于絕緣故障而流入地的電流。
3.9
對地泄漏電流 earth leakage current
無絕緣故障,從設備的帶電部件流入地的電流。
3.10
剩余電流動作斷路器residual current operated circuit-breaker
用于接通、承載和分斷正常工作條件下電流,以及在規定條件下當剩余電流達到規定值時,使觸頭斷開的機械開關電器。
3.11
剩余電流動作繼電器 residual current operated relay
在規定的條件下,當剩余電流達到規定值時,發出動作指令的電器。
3.12
負荷群group of loads
具有共同分支點的所有電力負荷的集合。
3.13
分級保護selective protection
RCD分別裝設在電源端、負荷群首端、負荷端,構成兩級及以上串聯保護系統,且各級RCD的主回路額定電流值、剩余電流動作值與動作時間協調配合,實現具有選擇性的分級保護。
3.14
總保護 main protection
安裝在配電臺區低壓側的第一級剩余電流動作保護器,亦稱總保(一級保護)。
3.15
中級保護middle protection
安裝在總保和戶保之間的低壓干線或分支線的剩余電流動作保護器,亦稱中保(二級保護)。中保因安裝地點、接線方式不同,可分為“三相中?!焙汀皢蜗嘀斜!?。
3.16
末端保護end protection
末端保護是指住宅配電保護(或稱戶保)或單臺用電設備的保護(三級保護)。
3.17
不帶過電流保護的剩余電流動作斷路器(RCCB) residual current operated circuit-breaker without integral overcurrent protection
不能執行過載和/或短路保護功能的剩余電流動作斷路器。
3.18
帶過電流保護的剩余電流動作斷路器(RCBO)residual current operated circuit-breaker with inte-gral overcurrent protection
能執行過載和/或短路保護功能的剩余電流動作斷路器。
3.19
動作功能與電源電壓無關的RCD RCD's functionally independent of line voltage
其檢測、判斷和分斷功能與電源電壓無關的RCD。
3.20
動作功能與電源電壓有關的RCD RCD's functionally dependent on line voltage
其檢測、判斷和分斷功能與電源電壓有關的RCD。
3.21
RCD的分斷時間break time of RCD
從突然施加剩余動作電流的瞬間起到所有極電弧熄滅瞬間為止所經過的時間。
3.22
極限不驅動時間limit non-actuating time
對RCD施加一個大于剩余不動作電流的剩余電流值而不使RCD動作的最大延時時間。
3.23
延時型RCD time-delay RCD
專門設計的對應于一個給定的剩余電流值,能達到一個預定的極限不驅動時間的RCD。
3.24
AC型RCD type AC residual current device
對突然施加或緩慢上升的剩余正弦交流電流能確保脫扣的RCD。
3.25
A型RCD type A residual current device
對突然施加或緩慢上升的剩余正弦交流電流和剩余脈動直流電流,能確保脫扣的RCD。
3.26
B型RCD type B residual current device
對突然施加或緩慢上升的剩余正弦交流電流、剩余脈動直流和平滑直流電流,能確保脫扣的RCD。
3.27
脈動直流電流pulsating direct current
在每一個額定工頻周期內,用角度表示至少為150°的一段時間間隔內電流值為0或不超過直流0.006 A的脈動波形電流。
3.28
試驗裝置test device
裝設在RCD內的模擬RCD在規定條件下動作的剩余電流條件的裝置。
3.29
組合式RCD assemble type residual operated protection devices
用剩余電流互感器、剩余電流動作繼電器、斷路器、報警或通信裝置等獨立部件分別安裝,通過電氣連接組合成的RCD。
3.30
移動式RCD portable move type residual current operated protective devices
可移動使用的RCD。
4 RCD的應用
4.1 對直接接觸電擊事故的防護
4.1 對直接接觸電擊事故的防護
在直接接觸電擊事故的防護中,RCD只作為直接接觸電擊事故基本防護措施的補充保護措施(不包括對相與相、相與N線間形成的直接接觸電擊事故的保護)。
用于直接接觸電擊事故防護時,應選用無延時的RCD,其額定剩余動作電流不超過30 mA。
4.2對間接接觸電擊事故的防護
4.2.1 一般要求
間接接觸電擊事故防護的主要措施是采用自動切斷電源的保護方式,以防止由于電氣設備絕緣損壞發生接地故障時,電氣設備的外露可接近導體持續帶有危險電壓而產生有害影響或電氣設備損壞事故。當電路發生絕緣損壞造成接地故障,其接地故障電流值小于過電流保護裝置的動作電流值時,應安裝RCD。
RCD用于間接接觸電擊事故防護時,應正確地與電網系統接地型式(電網系統接地的型式符合GB 14050—2008中4.1、4.2、4.3的規定,見附錄A)相配合。
4.2.2對TN系統的防護要求
4.2.2.1采用RCD的TN-C系統,應根據電擊防護措施的具體情況,將電氣設備外露可接近導體獨立接地,形成局部TT系統。
4.2.2.2在TN系統中,應將TN-C系統改造為TN-C-S、TN-S系統或局部TT系統后,方可安裝使用RCD。在TN-C-S系統中,RCD只允許使用在N線與PE線分開部分。
4.2.3對TT系統的防護要求
TT系統的電氣線路或電氣設備應裝設RCD作為防電擊事故的保護措施。
4.2.4對IT系統的防護要求
IT系統的電氣線路或電氣設備可以針對外露的可接觸不同電位的導電部分保護性安裝RCD。
4.3分級保護
低壓供用電系統中為了縮小發生人身電擊事故和接地故障切斷電源時引起的停電范圍,RCD應采用分級保護:
a) 分級保護方式(參見附錄C)的選擇應根據用電負荷和線路具體情況、被保護設備和場所的需要設置,形成由總保護、中級保護、末端保護組成兩級或三級保護。
b) 各級RCD的動作電流值與動作時間應協調配合,實現具有動作選擇性的分級保護。
c) RCD的分級保護應以末端保護為基礎。末端保護上一級保護的保護范圍應根據負荷分布的具體情況確定其保護范圍。
d) 為防止配電線路發生接地故障導致人身電擊事故,可根據線路的具體情況,采用分級保護。
e) 企事業單位的建筑物和住宅應采用分級保護。
4.4應安裝RCD的設備和場所
4.4.1末端保護
下列設備和場所應安裝末端保護RCD:
a) 屬于I類的移動式電氣設備及手持式電動工具1);
b)工業生產用的電氣設備;
c)施工工地的電氣機械設備;
d)安裝在戶外的電氣裝置;
e) 臨時用電的電氣設備;
f) 機關、學校、賓館、飯店、企事業單位和住宅等除壁掛式空調電源插座外的其他電源插座或插座回路;
g)游泳池、噴水池、浴室、浴池的電氣設備2);
h)安裝在水中的供電線路和設備;
i) 醫院中可能直接接觸人體的醫用電氣設備3);
j) 農業生產用的電氣設備;
k)水產品加工用電;
l) 其他需要安裝RCD的場所。
4.4.2 線路保護
低壓配電線路根據具體情況采用二級或三級保護時,在電源端、負荷群首端或線路末端(農業生產設備的電源配電箱)安裝RCD。
4.5可不裝RCD的情況
具備下列條件的電氣設備和場所,可不裝RCD:
a) 使用安全電壓供電的電氣設備;
1)參照GB/T 17045,電氣產品分為四類。其中I類產品的防電擊保護不僅依靠設備的基本絕緣,而且還應包含一個附加的安全預防措施,該措施是將可能觸及的可導電的零件與已安裝的固定線路中的保護線或TT系統的獨立接地裝置聯接起來,以使可觸及的可導電零件在基本絕緣損壞的事故中不帶有危險電壓。
2)指相關規定屬于應安裝保護裝置區域內的電氣設備。
3)指GB 9706.1—2007中H類醫用設備。
b)一般環境條件下使用的具有加強絕緣(雙重絕緣)的電氣設備(如II類和Ⅲ類電器等);
c)使用隔離變壓器且二次側為不接地系統供電的電氣設備;
d)具有非導電條件場所的電氣設備;
e)在沒有間接接觸電擊危險場所的電氣設備。
5 RCD的選用
5.1 RCD的技術條件
應符合GB/Z 6829、GB/T 10963.1、GB/T 14048.2、GB/T 16916、GB/T 16917、GB/T 20044、GB/T 28527、GB/T 22794、GB/T 22387等標準的規定,并通過中國國家強制性產品認證。
5.2 RCD的技術參數
RCD的技術參數額定值(見附錄B)應與被保護線路或設備的技術參數和安裝使用的具體條件相配合。
5.3按電氣設備的供電方式選用RCD
按電氣設備的供電方式,選用相應的RCD:
a)單相220 V電源供電的電氣設備,應選用二極二線式RCD;
b) 三相三線式380 V電源供電的電氣設備,應選用三極三線式RCD;
c)三相四線式220 V電源供電的電氣設備,三相設備與單相設備共用的電路應選用三極四線或四極四線式RCD。
5.4 RCD的額定動作電流選擇
RCD額定動作電流的選擇,應考慮下列因素:
a)要充分考慮電氣線路和設備的對地泄漏電流值,必要時可通過實際測量取得被保護線路或設備的對地泄漏電流;
b) 因季節和天氣變化引起對地泄漏電流值變化時,應考慮采用動作電流可調式RCD;
c) 當使用在有電力線載波應用等對線路漏電流有影響的場合時,應考慮非工頻泄漏電流的影響因素。
5.5采用分級保護方式
采用分級保護方式時,安裝使用前應利用試驗裝置進行串聯模擬分級動作試驗,保證其動作特性協調配合。
5.6 根據電氣設備的工作環境條件選用RCD
RCD的選用,應根據如下電氣設備的工作環境:
a)RCD應與使用環境條件相適應;
b)對電源電壓偏差在標準范圍內的地區的電氣設備應選用動作功能與電源電壓有關的RCD,否則應優先選用動作功能與電源電壓無關的RCD;
c) 特殊使用條件(超出或由RCD相關產品國家標準,如:GB/Z 6829、GB/T 14048.2、GB/T 16916、GB/T 18917等規定的“使用的標準工作條件”)下,應選用環境指標合適的RCD,并采取適當的措施,以確保RCD正常工作;
d) 對于家用電器保護的RCD必要時可選用滿足過電壓保護的RCD;
e) 安裝在易燃、易爆、潮濕或有腐蝕性氣體等惡劣環境中的RCD,應根據有關標準選用特殊防護條件的RCD,或采取相應的防護措施。
5.7 RCD動作參數的選擇
RCD動作參數的選擇,應考慮如下因素:
a) 手持式電動工具、移動電器、家用電器等設備應優先選用額定剩余動作電流不大于30 mA、無延時的RCD;
b)單臺電氣機械設備,可根據其容量大小選用額定剩余動作電流30 mA以上、100 mA及以下、無延時RCD;
c) 電氣線路或多臺電氣設備(或多住戶)的電源端,其動作電流和動作時間應按被保護線路和設備的具體情況及其泄漏電流值確定。必要時應選用動作電流可調和延時動作型的RCD;
d) 在采用分級保護方式時,上下級RCD的動作時間差不得小于0.1 s。上一級RCD的極限不驅動時間應大于下一級RCD的動作時間,且時間差應盡量?。? e) 選用的RCD的額定剩余不動作電流,應不小于被保護電氣線路和設備的正常運行時泄漏電流最大值的2倍;
f) 除末端保護外,各級RCD應選用低靈敏度延時型的保護裝置。且各級保護裝置的動作特性應協調配合,實現具有選擇性的分級保護。
5.8 特殊負荷和場所的RCD選用
4.4.1的i)中所列醫院中的醫用設備安裝RCD時,應選用額定剩余動作電流為10 mA、無延時的RCD。
安裝在潮濕場所的電氣設備應選用額定剩余動作電流小于30 mA、無延時的RCD。
安裝在游泳池、水景噴水池、水上游樂園、浴室、溫室養殖與育苗、水產品加工區等特定區域的電氣設備應選用額定剩余動作電流為10 mA、無延的RCD。
在金屬物體上工作,操作手持式電動工具或使用非安全電壓的行燈時,應選用額定剩余動作電流為10 mA,無延時的RCD。
連接室外架空線路的電氣設備,可能發生沖擊過電壓時,可采取特殊的保護措施(例如:采用電涌保護器等過電壓保護裝置),并選用增強耐誤脫扣能力的RCD。
一般情況下,選用AC型RCD。對應用電子元器件較多的電氣設備,電源裝置故障含有脈動直流分量時,應選用A型RCD。對負荷帶有變頻器、三相交流整流器、逆變換器、UPS裝置及特殊醫療設備(例如:X射線設備、CT)等產生平滑直流剩余電流的電氣設備,應選用特殊的對脈動直流剩余電流和平滑直流剩余電流均能動作的B型RCD。
對弧焊變壓器應采用專用的防電擊保護裝置。
各級RCD,可有條件選配具有信息(如運行時間、停運時間、運行參數、剩余電流值等)顯示、測量、存儲或通信功能的RCD。
6 RCD的安裝
6.1 RCD安裝要求
RCD安裝要求如下:
a) RCD安裝應符合GB/Z 6829、GB/T 14048.1、GB/T 16916、GB/T 16917、GB/T 20044、GB/T 28527、GB/T 22794、GB/T 22387等有關標準的要求;
b)RCD安裝應充分考慮供電方式、供電電壓、系統接地方式及保護方式;
c)RCD的型式、額定電壓、額定電流、短路分斷能力、額定剩余動作電流、分斷時間應滿足被保護線路和電氣設備的要求;
d) RCD在不同的系統接地方式中應正確接線。單相、三相三線、三相四線供電系統中的正確接線方式如表1;
e)采用不帶過電流保護功能,且需輔助電源的RCD時,與其配合的過電流保護元件(熔斷器)應安裝在RCD的負荷側。
6.2 RCD對電網的要求
RCD對電網的要求如下:
a)RCD負荷側的N線,只能作為中性線,不得與其他回路共用,且不能重復接地。
b)TN-C系統的配電線路因運行需要,在N線應有重復接地時,不應將RCD作為線路電源端保護。
c) 當電氣設備裝有高靈敏度RCD時,電氣設備獨立接地裝置的接地電阻,可適當放寬,但應滿足式(1)要求:
RA×IΔn≤50 V (1)
式中:
RA——接地裝置的接地電阻和外露可接近導體的接地導體的電阻總和,單位為歐姆(Ω);
IΔn——RCD的額定剩余動作電流,單位為安培(A)。
d)安裝RCD的電氣線路或設備,在正常運行時,其泄漏電流應控制在允許范圍內,同時應滿足5.7 e)的要求。當泄漏電流大于允許值時,應對線路或設備進行檢查或更換;
e) 安裝RCD的電動機及其他電氣設備在正常運行時的絕緣電阻不應小于0.5 MΩ。
6.3安裝RCD的施工要求
安裝RCD的施工要求如下:
a)RCD標有電源側和負荷側時,應按規定安裝接線,不得反接。
b)安裝剩余電流斷路器時,應按要求在電弧噴出方向有足夠的飛弧距離。
c) 組合式RCD其控制回路的連接,應使用截面積不小于1.5 mm2的銅導線。
d) RCD安裝時,應嚴格區分N線和PE線,三極四線式或四極四線式RCD的N線應接入保護裝置。通過RCD的N線,不得作為PE線,不得重復接地或接設備外露可接近導體。PE線不得接入RCD。
e)安裝RCD后,對原有的線路和設備的接地保護措施,應按6.1 d)、6.2 b)及6.3 d)的要求進行檢查和調整。
f)RCD投入運行前,應操作試驗按鈕,檢驗RCD的工作特性,確認能正常動作后,才允許投入正常運行。
g)RCD安裝后的檢驗項目:
1) 用試驗按鈕試驗1次,應正確動作;
2) RCD帶額定負荷電流分合1次,應可靠動作。
h)RCD的安裝應由經技術考核合格的專業人員進行。
i) 產權所有者應建立保存RCD的安裝及試驗記錄。
RCD接線方式見表1。
表1 RCD接線方式
接地類型
單相(二極)
三相
三線(三極)
四線(三極或四極)
注1:L1、L2、L3為相線;N為中性線;PE為保護線;PEN為中性線和保護線合一; 為單相或三相電氣設備; 為單相照明設備;RCD為剩余電流保護裝置; 為不與系統中性接地點相連的單獨接地裝置,作保護接地用。
注2:單相負載或三相負載在不同的接地保護系統中的接線方式圖中,左側設備為未裝有RCD,中間和右側為裝用RCD的接線圖。
注3:在TN-C-S系統中使用RCD的電氣設備,其外露可接近導體的保護線應接在單獨接地裝置上而形成局部TT系統,如TN-C-S系統接線方式圖中的右側設備帶*的接線方式。
注4:表中TN-S及TN-C-S接地型式,單相和三相負荷的接線圖中的中間和右側接線圖為根據現場情況,可任選其一接地方式。
7 RCD的運行和管理
RCD投入運行后,運維管理者應對剩余電流動作保護器建立相應的管理制度,并建立動作記錄。
RCD投入運行后,應定期操作試驗按鈕,檢查其動作特性是否正常。雷擊活動期和用電高峰期應增加試驗次數。
用于手持式電動工具和移動式電氣設備和不連續使用的RCD,應在每次使用前進行試驗。
為檢驗剩余電流裝置在運行中的動作特性及其變化,運行管理者應配置專用測試儀器,并應定期進行動作特性試驗。
動作特性試驗項目:
a)測試剩余動作電流值;
b)測試分斷時間;
c)測試極限不驅動時間。
電子式RCD,根據電子元器件有效工作壽命,工作年限一般為6年。超過規定年限應進行全面檢測,根據檢測結果,決定可否繼續運行。
因各種原因停運的RCD再次使用前,應進行動作特性試驗,檢查裝置的動作情況是否正常。
RCD進行動作特性試驗時,應使用經國家有關部門檢測合格的專用測試設備,由專業人員進行。
嚴禁利用相線直接對地短路或利用動物作為試驗物的方法。
RCD動作后,經檢查未發現動作原因時,允許試送電一次。如果再次動作,應查明原因找出故障,不得連續強行送電。必要時對其進行動作特性試驗,經檢查確認RCD本身發生故障時,應在最短時間內予以更換。嚴禁退出運行、私自撤除或強行送電。
RCD運行管理者應定期檢查分析RCD的使用情況,對已發現的有故障的RCD應立即更換。
RCD運行中遇有異?,F象,應由專業人員進行檢查處理,以免擴大事故范圍。
在RCD的保護范圍內發生電擊傷亡事故,應檢查RCD的動作情況,分析未能起到保護作用的原因,在未調查前,不得拆動RCD。
對剩余電流斷路器、剩余電流繼電器和接觸器、斷路器組成的組合式電器,除定期進行剩余電流動作試驗外,對斷路器,接觸器部分應按有關規程進行檢查維護。
RCD損壞后,應由專業人員進行維修。
有條件時,對RCD運行狀況可以進行集中監控和管理。